What is the minimum exhaust ventilation flow rate required for a print and/or photocopy room?

The exhaust ventilation flow rate for a print and/or photocopy room must be at least 5l/s/m2 AND at least 10% greater than the supply rate of air. This ensures the space is negatively pressurised and pollutants do not escape to neighbouring areas. 

Refer to AS1668.2- 2012 for further details.





Rating Tools

This FAQ is related to the following Rating Tools, Categories or Credits:

  • Green Star - Design & As Built v1 / Indoor Environment Quality / 9.3 Indoor Air Quality - Exhaust or Elimination of Pollutants
  • Green Star - Design & As Built v1.1 / Indoor Environment Quality / 9.3 Indoor Air Quality - Exhaust or Elimination of Pollutants
  • Green Star - Design & As Built v1.2 / Indoor Environment Quality / 9.3 Indoor Air Quality - Exhaust or Elimination of Pollutants
  • Green Star - Design & As Built v1.3 / Indoor Environment Quality / 9.3 Exhaust or Elimination of Pollutants
  • Green Star - Interiors v1 / Indoor Environment Quality / 8.3 Indoor Air Quality - Exhaust or Elimination of Pollutants
  • Green Star - Interiors v1.1 / Indoor Environment Quality / 8.3 Indoor Air Quality - Exhaust or Elimination of Pollutants
  • Green Star - Interiors v1.2 / Indoor Environment Quality / 8.3 Indoor Air Quality - Exhaust or Elimination of Pollutants
  • Green Star - Interiors v1.3 / Indoor Environment Quality / 8.3 Exhaust or Elimination of Pollutants


Disclaimer

These FAQs are:

  • provided as additional technical assistance for Green Star users.
  • optional and free to use on Green Star projects.

When used on Green Star projects, make sure to:
  • state the FAQ number on the Submission Template.
  • click on "Download" to save the FAQ.
  • include the PDF in the submission.

The GBCA reserves the right to add or remove FAQ at our discretion.





Have more questions?

Submit a question by selecting an option below: