Can a project conduct air tightness testing on a whole building by using Method 2 from AS/NZS ISO 9972:2015?
Yes. A project may test a whole building according to AS/NZS ISO 9972 Method 2 where diagnostic techniques are used to highlight performance differences related to HVAC. Techniques in standards such as ASTM E1186 may be used to document leakage, or, comparative quantitative measurements can be used to highlight performance differences.
All other requirements for quantitative whole-building tests done according to AS/NZS ISO 9972 must be satisfied, including documentation of all system preparations, regardless of which Method is used.
Recommended evidence
Supporting documentation demonstrating the following has occurred to identify the performance differences related to HVAC:
- Document any differences in building preparation resulting from use of Method 2
- Remove preparations from, or perform diagnostics on, at least one unit from each category of HVAC systems and document leaks identified
- Determine and document the likely source of leak
This FAQ is related to the following Rating Tools, Categories or Credits:
- Green Star - Design & As Built v1 / Management
- Green Star - Design & As Built v1.1 / Management
- Green Star - Design & As Built v1.2 / Management
- Green Star - Design & As Built v1.3 / Management
- Green Star Buildings v1 / Responsible / 3 Verification and Handover
- Green Star Buildings v1.0 / Responsible / 3 Verification and Handover
These FAQs are:
- provided as additional technical assistance for Green Star users.
- optional and free to use on Green Star projects.
When used on Green Star projects, make sure to:
- state the FAQ number on the Submission Template.
- click on "Download" to save the FAQ.
- include the PDF in the submission.
The GBCA reserves the right to add or remove FAQ at our discretion.
Submit a question by selecting an option below: